|
Class II, Div. 1 Purge/Pressurization
Protection Method: Type "X" Pressurization System
Powering Method: Automatic Power Control Unit or Local Disconnect
Switch System Status: Protected Equipment De-energized Alarm System and Air Supply On
- Remove hazardous substance from the protected enclosure. A vacuum device is the preferred tool for dust removal.
- Check operation of enclosure pressure relief device (if utilized) and seal the protected enclosure.
- Pressurize the protected enclosure to set and maintain a positive pressure of 0.50 inches (12.7 mm) of water.
- System will apply power automatically when pressure is set and maintained at a positive pressure of 0.50 inches (12.7 mm) of water.
- Loss of pressurization must automatically de-energize protected equipment power immediately.
 |
Exception: Automatic power control is not required if the enclosure is designed to prevent the entrance of dust and the pressurization system activates an audible or visual alarm in a constantly attended location.
|
- Equipment that may overload or overheat, such as motors or transformers, require thermal overload cutoff switches or alarms.
Class I, Div 1 Purge/Pressurization
Protection Method: Type "X" Purge/Pressurization System
Powering Method: Automatic Power Control Unit
System Status: Protected Equipment De-energized Alarm System and Air Supply On
- Check operation of enclosure pressure relief device (if utilized) and seal the protected enclosure.
- Pressurize the protected enclosure to set and maintain a minimum positive pressure of 0.10 inches (2.5 mm) of water.
- Exchange the recommended volumes of purging gas.
- System will deny power automatically until recommended volume exchange is complete and pressure is set and maintained at a minimum positive pressure of 0.10 inches (2.5 mm) of water.
- Loss of pressurization must automatically de-energize protected equipment power immediately.
 |
Exception: Power may be maintained for a short period if immediate loss of power would result in a more hazardous condition and if the system activates both audible and visual alarms in a constantly attended location.
|
- Equipment that may overload or overheat, such as motors or transformers, require thermal overload cutoff switches or alarms.
Return to Top
Class I, Div 2 Purge/Pressurization
Protection Method: Type "Z" Purge/Pressurization System
Powering Method: Local Disconnect Switch
System Status: Protected Equipment De-energized Alarm System and Air Supply On
- Check operation of enclosure pressure relief device (if utilized) and seal the protected enclosure.
- Pressurize the protected enclosure to set and maintain a minimum positive pressure of 0.10 inches (2.5 mm) of water.
- Exchange the recommended volumes of purging gas.
 |
Exception: Power may be energized immediately if the protected enclosure atmosphere is known to be nonflammable.
|
- Energize the protected equipment power manually with a disconnect switch or breaker rated for the hazardous location.
- Loss of pressurization requires immediate attention or the manual de-energizing of protected equipment power.
- Excessively hot equipment must be isolated in a separate protected enclosure, unless the enclosure is marked with a warning which indicates a required cool-down time period before access.
Class II, Div. 2 Pressurization
Protection Method: Type "Z" Pressurization System
Powering Method: Local Disconnect Switch
System Status: Protected Equipment De-energized Alarm System and Air Supply On
- Remove hazardous substance from the protected enclosure. A vacuum device is the preferred tool for dust removal.
- Check operation of enclosure pressure relief device (if utilized) and seal the protected enclosure.
- Pressurize the protected enclosure to set and maintain a positive pressure of 0.50 inches (12.7 mm) of water.
- Energize the protected equipment power manually with a disconnect switch or breaker rated for the hazardous location.
- Loss of pressurization requires immediate attention or the manual de-energizing of protected equipment power.
- Excessively hot equipment must be isolated in a separate protected enclosure, unless the enclosure is marked with a warning which indicates a required cool-down time period before access.
Return to Top
|